THE CEILING-MOUNTED MONOBLOCK UNIT
IDEAL FOR REDUCED SPACES.
OPTIMISED FOR EACH IMPLEMENTATION
UNIQUE AND SMART
CEILING MOUNTING
Ceiling mounting is the ideal installation solution
whenever space is limited.
Additionally the monoblock unit is operated
by a remote control panel.
Forward-thinking:
our monoblock unit is designed for the future.
Conditions for volume calculation
Medium Temperature
Cold room insulation: 100 mm
Charge density: 250 kg/m³
Specific heat of the product: 3,22kJ/kg*K
Product inlet temperature: +15 °C
Compressor running time: 18 h
Goods transshipment: 7%
Low Temperature
Cold room insulation: 100 mm
Charge density: 250 kg/m³
Specific heat of the product: 1,84 kJ/kg*K
Product inlet temperature: -10 °C
Compressor running time: 18 h
Goods transshipment: 7%
Cold room volume and cooling capacity
Ambient temperature [°C] | Cold room temperature [°C] | Polarik 7TN1 | Polarik 15TN2 | Polarik 20TN2 |
|
---|---|---|---|---|---|
+25 | -5 | m3 | 6,8 | 13,8 | 16,4 |
w | 1420 | 1750 | 2260 | ||
0 | m3 | 7,4 | 15,8 | 21,4 | |
w | 1840 | 2260 | 3020 | ||
+5 | m3 | 8,2 | 18,7 | 24,8 | |
w | 2200 | 2680 | 3900 | ||
+35 | -5 | m3 | 5,8 | 12,5 | 15,7 |
w | 1220 | 1520 | 1880 | ||
0 | m3 | 6,8 | 14,1 | 18,4 | |
w | 1450 | 1960 | 2520 | ||
+5 | m3 | 7,5 | 15,2 | 20,6 | |
w | 1880 | 2450 | 3380 | ||
+43 | -5 | m3 | 5,1 | 8,1 | 13,8 |
w | 940 | 1250 | 1680 | ||
0 | m3 | 5,9 | 10,8 | 14,9 | |
w | 1220 | 1680 | 2230 | ||
+5 | m3 | 7,1 | 12,1 | 16,3 | |
w | 1530 | 2080 | 3120 |
Ambient temperature [°C] | Cold room temperature [°C] | Polarik 5TL1 | Polarik 10TL2 |
|
---|---|---|---|---|
+25 | -25 | m3 | 6,2 | 11,7 |
w | 620 | 1920 | ||
-20 | m3 | 7,9 | 13,6 | |
w | 860 | 2540 | ||
-15 | m3 | 8,2 | 15,4 | |
w | 1140 | 3140 | ||
+35 | -25 | m3 | 3,8 | 7,3 |
w | 520 | 1450 | ||
-20 | m3 | 4,5 | 9,5 | |
w | 710 | 2080 | ||
-15 | m3 | 5,3 | 11,8 | |
w | 920 | 2600 |
Installation of the unit
TABLE FEATURES
Medium Temperature
Description | Unit | Polarik 7TN1 | Polarik 15TN2 | Polarik 20TN2 |
---|---|---|---|---|
Temperature range of the cold room | º C | MT + 10 º C / - 5 º C | ||
Max. volume of the cold room | m³ | 7 | 15 | 20 |
Voltage | V | 1 ˜ 230 | 1 ˜ 230 | 3 ˜ 400 |
Frequency | Hz | 50 | 50 | 50 |
Cooling capacity | W | 1590 | 2079 | 2560 |
Heat output to the environment | W | 2291 | 2904 | 3690 |
Compressor energy consumption | W | 701 | 825 | 1130 |
EER1 | 2,27 | 2,52 | 2,27 | |
Current consumption LRA | A | 28 | 30 | 23 |
Current consumption FLA | A | 5,7 | 5,1 | 7,5 |
Type of defrosting | HG | HG | HG | |
Evaporator air flow | m³ / h | 750 | 1100 | 1100 |
Condenser air flow | m³ / h | 750 | 1100 | 1100 |
Degree of protection | IP | 34 | ||
Max. external temperature | º C | 43 | ||
Refrigerant | Type | R-513A | ||
GWP2 | 631,4 | |||
CO2 equivalent | t CO2 | 0,253 | 0,379 | 0,410 |
Amount of refrigerant | g | 400 | 600 | 650 |
Power supply cable length | m | 2 | 2 | 2 |
Evaporator air throw | m | 2,5 | 4 | 4 |
Dimensions drawings No. | 1 | 2 | 2 | |
Weight | kg | 86 | 112 | 114 |
Colour | RAL | 9010 / 7024 |
Low Temperature
Description | Unit | Polarik 5TL1 | Polarik 10TL2 |
---|---|---|---|
Temperature range of the cold room | º C | LT -15 º C / - 25 º C | |
Max. volume of the cold room | m³ | 5 | 10 |
Voltage | V | 1 ˜ 230 | 3 ˜ 400 |
Frequency | Hz | 50 | 50 |
Cooling capacity | W | 738 | 1622 |
Heat output to the environment | W | 1298 | 3205 |
Compressor energy consumption | W | 560 | 1583 |
EER1 | 1,32 | 1,21 | |
Current consumption LRA | A | 21 | 23 |
Current consumption FLA | A | 2,4 | 2,8 |
Type of defrosting | HG | HG | |
Evaporator air flow | m³ / h | 750 | 1100 |
Condenser air flow | m³ / h | 750 | 1100 |
Degree of protection | IP | 34 | |
Max. external temperature | º C | 35 | |
Refrigerant | Type | R-452A | |
GWP2 | 2140 | ||
CO2 equivalent | t CO2 | 0,642 | 1,498 |
Amount of refrigerant | g | 300 | 700 |
Power supply cable length | m | 2 | 2 |
Evaporator air throw | m | 2,5 | 4 |
Dimensions drawings No. | 1 | 2 | |
Weight | kg | 86 | 124 |
Colour | RAL | 9010 / 7024 |
Cooling capacity at an ambient temperature of +32 °C and at an internal temperature of the cold room of +2 °C (cold room with 100-mm insulation + insulated floor)
1 - EER - Efficiency value obtained from the ratio between energy consumption and cooling capacity 2 - GWP - Global warming potential
Cooling capacity at an ambient temperature of +32 °C and at an internal temperature of the cold room of -18 °C (cold room with 100-mm insulation + insulated floor)
1 - EER - Efficiency value obtained from the ratio between energy consumption and cooling capacity 2 - GWP - Global warming potential